LPJ系列 Class J 600Vac 慢速熔断器
-
Low-Peak™ LPJ Class J 600Vac/300Vdc, 1-60A, dual element, time-delay fuses
-
Low-Peak™ LPJ Class J 600Vac/300Vdc, 70-600A, dual element, time-delay fuses
Low-Peak™ LPJ Class J 600Vac/300Vdc, 1-60A, dual element, time-delay fuses
Catalog symbol :
-
LPJ-(amp)SP (non-indicating)
-
LPJ-(amp)SPI (indicating)
Description::
Bussmann® series Ultimate protection LPJ Class J dual element, current-limiting, time-delay fuses available with optional open fuse indication. Timedelay – 10 seconds (minimum) at 500% of rated current.
Specifications: Ratings
Volts
-
600Vac
-
300Vdc*
Amps : 1-60A
IR :
-
300kA Vac RMS Sym.
-
100kA Vdc
* Indicating versions not Vdc rated.
Agency information
-
UL® Listed, Guide JDDZ, File E4273
-
CSA® Certified, Class 1422-02, File 53787, Class J per CSA 22.2 No. 248.
-
CE
-
RoHS compliant
Catalog numbers (amps) – non-indicating fuses
LPJ-1SP |
LPJ-3SP |
LPJ-7SP** |
LPJ-25SP** |
LPJ-1-1⁄4SP |
LPJ-3-2⁄10SP |
LPJ-8SP** |
LPJ-30SP** |
LPJ-1-6⁄10SP |
LPJ-3-1⁄2SP |
LPJ-9SP** |
LPJ-35SP** |
LPJ-1-8⁄10SP |
LPJ-4SP |
LPJ-10SP** |
LPJ-40SP** |
LPJ-2SP |
LPJ-4-1⁄2SP |
LPJ-12SP** |
LPJ-45SP** |
LPJ-2-1⁄4SP |
LPJ-5SP |
LPJ-15SP** |
LPJ-50SP** |
LPJ-2-1⁄2SP |
LPJ-5-6⁄10SP |
LPJ-17-1⁄2SP** |
LPJ-60SP** |
LPJ-2-8⁄10SP |
LPJ-6SP** |
LPJ-20SP** |
* Open fuse indication available by inserting the suffix “I,” e.g., LPJ-15SPI. Requires 75Vac minimum voltage. Indicating fuses are not Vdc rated.
Carton Quantity
Amp Rating |
Carton Qty. |
1-60A |
10 |
Features:
-
Industry’s only UL Listed and CSA Certified fuse with a 300kA interrupting rating that allows for simple, worry-free installation in virtually any application.
-
Fast short-circuit protection and dual-element, time-delay performance provide ultimate protection.
-
Reduces existing fuse inventory by up to 33% when upgrading to Low-Peak fuses.
-
Consistent 2:1 ampacity ratios for all Low-Peak fuses make selective coordination easy.
-
Long time-delay minimizes needless fuse openings due to temporary overloads and transient surges.
-
Current-limitation protects downstream components against damaging thermal and magnetic effects of short-circuit currents.
-
Dual-element fuses have lower resistance than ordinary fuses so they run cooler. They can often be sized for back-up protection against motor burnout from overload or single-phasing if other overload protective devices fail.
-
Proper sizing can provide “no damage” Type 2 coordinated protection for NEMA® and IEC® motor controllers.
-
Space-saving package for equipment downsizing.
Recommended fuse blocks and holders:
Fuse amps |
1-Pole |
2-Pole |
3-Pole |
Modular open blocks with optional covers |
|||
0-30 |
JM60030-1_ |
JM60030-2_ |
JM60030-3_ |
35-60 |
JM60060-1_ |
JM60060-2_ |
JM60060-3_ |
“Pyramid” blocks |
|||
0-30 |
— |
— |
JP60030-3_ |
CH holders |
|||
0-30 |
CH30J1_ |
CH30J2_ |
CH30J3_ |
35-60 |
CH60J1_ |
CH60J2_ |
CH60J3_ |
Safety J™ holders |
|||
0-30 |
JT60030_ |
— |
— |
35-60 |
JT60060_ |
— |
— |
For additional information on the Class J fuse blocks and holders, see data sheets no. 10289 (modular open blocks), no.1108 (pyramid blocks), no. 2144 (CH) and no. 1152 (Safety J).
Fuse reducers for Class J fuses:
Equipment fuse clips |
Desired fuse (case size) |
Catalog no. (pairs) |
60A |
30A |
J-63 |
100A |
30A |
J-13 |
60A |
J-16 |
|
200A |
60A |
J-26+ |
† Not for bolt-in applications.
Current-limiting effects:
Prospective S.C.C. |
Let-through current |
||
(apparent RMS symmetrical vs. fuse rating) |
|||
15A |
30A |
60A |
|
1000 |
1000 |
1000 |
1000 |
3000 |
1000 |
1000 |
1000 |
5000 |
1000 |
1000 |
1000 |
10000 |
1000 |
1000 |
2000 |
15000 |
1000 |
1000 |
2000 |
20000 |
1000 |
1000 |
2000 |
25000 |
1000 |
1000 |
2000 |
30000 |
1000 |
1000 |
2000 |
35000 |
1000 |
1000 |
2000 |
40000 |
1000 |
2000 |
3000 |
50000 |
1000 |
2000 |
3000 |
60000 |
1000 |
2000 |
3000 |
80000 |
1000 |
2000 |
3000 |
100000 |
1000 |
2000 |
4000 |
150000 |
1000 |
2000 |
4000 |
200000 |
2000 |
3000 |
4000 |
250000 |
2000 |
3000 |
5000 |
300000 |
2000 |
3000 |
5000 |
Low-Peak™ LPJ Class J 600Vac/300Vdc, 70-600A, dual element, time-delay fuses
Catalog symbols:
-
LPJ-(amp)SP (non-indicating)
-
LPJ-(amp)SPI (indicating)
Description:
Bussmann® series Ultimate protection LPJ Class J dual element, current-limiting, time-delay fuses available with optional open fuse indication. Timedelay – 10 seconds (minimum) at 500% of rated current.
Specifications:
Ratings
Volts :
-
600Vac
-
300Vdc*
Amps : 70-600A
IR
-
300kA Vac RMS Sym.
-
100kA Vdc
* Indicating versions not Vdc rated
Agency information :
-
UL® Listed, Guide JDDZ, File E4273
-
CSA® Certified, Class 1422-02, File 53787, Class J per CSA C22.2 No. 248.8
-
CE
-
RoHS compliant
Catalog numbers (amps) – non-indicating fuses
LPJ-70SP |
LPJ-125SP |
LPJ-250SP |
LPJ-500SP |
LPJ-80SP |
LPJ-150SP |
LPJ-300SP |
LPJ-600SP |
LPJ-90SP |
LPJ-175SP |
LPJ-350SP |
|
LPJ-100SP |
LPJ-200SP** |
LPJ-400SP |
|
LPJ-110SP |
LPJ-225SP |
LPJ-450SP |
*Open fuse indication available on all part numbers by inserting the suffix “I,” e.g., LPJ-90SPI. Requires 75Vac minimum voltage. Indicating fuses are not Vdc rated.
Carton Quantity :
Amp Rating |
Carton Qty. |
7-200A |
5 |
225-600A |
1 |
Features:
-
Industry’s only UL Listed and CSA Certified fuse with a 300kA interrupting rating that allows for simple, worry-free installation in virtually any application.
-
Fast short-circuit protection and dual-element, time-delay performance provide ultimate protection.
-
Reduces existing fuse inventory by up to 33% when upgrading to Low-Peak fuses.
-
Consistent 2:1 ampacity ratios for all Low-Peak fuses make selective coordination easy.
-
Long time-delay minimizes needless fuse openings due to temporary overloads and transient surges.
-
Current-limitation protects downstream components against damaging thermal and magnetic effects of short-circuit currents.
-
Dual-element fuses have lower resistance than ordinary fuses so they run cooler.
-
Can often be sized for back-up protection against motor burnout from overload or single-phasing if other overload protective devices fail.
-
Proper sizing can provide “no damage” Type 2 coordinated protection for NEMA® and IEC® motor controllers.
-
Space-saving package for equipment downsizing.
Recommended fuse blocks: :
Fuse amps |
1-Pole |
2-Pole |
3-Pole |
70-100 |
JM60100-1CR |
JM60100-2CR |
JM60100-3CR |
110-200 |
JM60200-1CR |
JM60200-2CR |
JM60200-3CR |
225-400 |
JM60400-1CR |
JM60400-2CR |
JM60400-3CR |
450-600 |
JM60600-1CR |
JM60600-2CR |
JM60600-3CR |
For additional information on the JM fuse blocks, see product brochure no. 3192
Fuse reducers for Class J fuses:
Equipment fuse clips |
Desired fuse (case size) |
Catalog no. (pairs) |
100A |
30A |
J-13 |
60A |
J-16 |
|
200A |
60A |
J-26+ |
100A |
J-21+ |
|
400A |
100A |
J-41+ |
200A |
J-42+ |
|
600A |
200A |
J-62+ |
400A |
J-64+ |
Current-limiting effects:
Prospective S.C.C. |
Let-through current |
|||
(apparent RMS symmetrical vs. fuse rating) |
||||
100A |
200A |
400A |
600A |
|
1000 |
1000 |
1000 |
1000 |
1000 |
3000 |
2000 |
2000 |
3000 |
3000 |
5000 |
2000 |
3000 |
5000 |
5000 |
10000 |
2000 |
4000 |
6000 |
8000 |
15000 |
3000 |
4000 |
7000 |
9000 |
20000 |
3000 |
4000 |
7000 |
10000 |
25000 |
3000 |
5000 |
8000 |
10000 |
30000 |
3000 |
5000 |
8000 |
11000 |
35000 |
4000 |
5000 |
9000 |
12000 |
40000 |
4000 |
6000 |
9000 |
12000 |
50000 |
4000 |
6000 |
10000 |
13000 |
60000 |
4000 |
6000 |
11000 |
14000 |
80000 |
5000 |
7000 |
12000 |
15000 |
100000 |
5000 |
8000 |
12000 |
17000 |
150000 |
6000 |
9000 |
14000 |
19000 |
200000 |
6000 |
9000 |
16000 |
21000 |
250000 |
7000 |
10000 |
17000 |
23000 |
300000 |
7000 |
11000 |
18000 |
24000 |
系列:LPJ-SP系列,慢速延时熔断器
电流:1-600A
电压:600Vac (or less); 300Vdc (or less)
分断容量:300KA VAC RMS SYM /100KA VDC
认证:CE. UL.CSA